Page 221 - EPR Catalog 2015
P. 221
CP-E range
Technical data
Data at Ta = 25 °C, Uin = 230 V AC and rated values, unless otherwise indicated
Type CP-E 5/3.0 CP-E 12/2.5 CP-E 12/10.0
General data
Power dissipation typ. 5 W typ. 5.6 W typ. 24 W
Efficiency
Duty time typ. 75 % typ. 84 % typ. 84 %
Dimensions (W x H x D)
100 %
Weight
Material of housing 22.5 x 90 x 114 mm 40.5 x 90 x 114 mm 63.2 x 123.6 x 123.6 mm
Mounting (0.89 x 3.54 x 4.49 in) (1.59 x 3.54 x 4.49 in) (2.49 x 4.87 x 4.87 in)
Mounting position
Minimum distance to other units 0.144 kg (0.317 lb) 0.287 kg (0.633 lb) 0.888 kg (1.958 lb)
Degree of protection
Protection class Plastic Metal 3
DIN rail (IEC/EN 60715), snap-on mounting without any tool
horizontal
horizontal / vertical 25 mm / 25 mm (0.98 in / 0.98 in)
housing / terminals IP20 / IP20
I
Electrical connection - input circuit / output circuit
Wire size fine-strand with wire end ferrule 0.2-2.5 mm2 (24-14 AWG) 0.2-4 mm² (24-11 AWG)
fine-strand without wire end ferrule 0.2-6 mm² (24-10 AWG)
rigid
Stripping length 6 mm (0.24 in) 8 mm (0.31 in)
Tightening torque input / output 0.6 Nm (5 lb.in) -40…+70 °C 1.0 Nm (9 lb.in) /
operation -20…+70 °C 0.62 Nm (5.5 lb.in)
Environmental data
Ambient temperature range -35…+70 °C
rated load -20...+60 °C -40...+60 °C -35...+60 °C
storage -20…+85 °C -40…+85 °C -40…+85 °C
Damp heat (cyclic) (IEC/EN 60068-2-30) 95 RH, % without condensation
Vibration (sinusoidal) (IEC/EN 60068-2-6) 10-500 Hz, 2 G, along X, Y, Z each axis, 60 min. for each axis
Shock (half-sine) (IEC/EN 60068-2-27) 15 G, 11 ms, 3 axes, 6 faces, 3 times for each face
Isolation data
Rated insulation voltage Ui input circuit / output circuit 3 kV AC
input / PE 1.5 kV AC
output / PE 0.5 kV AC; 0.71 kV DC
Pollution degree 2
Overvoltage category (UL/IEC/EN 60950-1) II
Standards EN 61204-3 EN 60950-1, UL 60950-1, UL 508,
Product standard EN 61558-1, EN 61558-2-17; EN 60204-1
Low Voltage Directive 2006/95/EC
EMC directive
RoHS directive 2004/108/EC
Electrical safety
2011/65/EC
Protective low voltage
EN 60950-1,
UL 60950-1, UL 508
SELV (EN 60950)
Electromagnetic compatibility IEC/EN 61000-6-2
Interference immunity to IEC/EN 61000-4-2 Level 4 (air discharge 15 kV / contact discharge 8 kV)
IEC/EN 61000-4-3 Level 3 (10 V/m)
electrostatic discharge
IEC/EN 61000-4-4 Level 4 (4 kV / 2,5 kHz) Level 4 (4 kV / 5 kHz)
radiated, radio-frequency, electromagnetic IEC/EN 61000-4-5 L-L Level 3 (2 kV) / L-PE Level 4 (4 kV)
field IEC/EN 61000-4-6 Level 3 (10 V)
electrical fast transient/burst
IEC/EN 61000-4-8 Level 4 (30 A/m)
surge
IEC/EN 61000-4-11 dip: >95 % 10 ms / >30 % 500 ms
conducted disturbances, induced by radio- interruptions: >95 % 5000 ms
frequency fields IEC/EN 61000-6-3
power frequency magnetic fields
IEC/CISPR 22, EN 55022 Class B
voltage dips, short interruptions and voltage
variations IEC/CISPR 22, EN 55022 Class B
Interference emission
high-frequency radiated IEC/EN 61000-3-2 Class D Class A Class D
high-frequency conducted
limits for harmonic current emissions
„Approvals and marks“ on page 3/4.
2CDC 110 004 C0210 | Catalog Electronic Products and Relays 2015 | ABB 3/22