CP-E range
Technical data
Data at Ta = 25 °C, Uin = 230 V AC and rated values, unless otherwise indicated
Type CP-E 5/3.0 CP-E 12/2.5 CP-E 12/10.0
Input circuit 100-240 V AC L, N
Rated input voltage Uin 115 / 230 V AC
Input voltage range 90-264 V AC / 85-264 V AC / auto select
120-375 V DC 90-375 V DC 90-132 V AC,
Frequency range AC 180-264 V AC /
Typical input current 47-63 Hz 210-375 V DC
3 at 115 V AC 335 mA 560 mA 2.2 A
0.83 A
Typical power consumption at 230 V AC 210 mA 330 mA 143 W
Inrush current limiting 24 A (max. 5 ms)
19.8 W 35.9 W 48 A (max. 5 ms)
Discharge current
at 115 V AC 10 A (max. 3 ms) 20 A (max. 3 ms) min. 25 ms
Power failure buffering time min. 30 ms
at 230 V AC 18 A (max. 3 ms) 40 A (max. 3 ms) 3.15 A slow-acting /
Internal input fuse 250 V AC
Power factor correction (PFC) input / output 0.25 mA yes, passive, 0.7
input / PE 3.5 mA
at 115 V AC min. 20 ms min. 20 ms
at 230 V AC min. 75 ms min. 30 ms
2 A slow-acting / 250 V AC
no
Indication of operational states green LED OK: V: OUTPUT OK: V: OUTPUT OK: V:
Output voltage output voltage OK
output voltage OK output voltage OK
Output circuit red LED LOW: V:
output voltage too low - OUTPUT LOW: V:
L+,L-
output voltage too low
L+, L+, L-, L-
Rated output voltage 5 V DC 12 V DC
Tolerance of the output voltage 0...+1 %
Adjustment range of the output voltage 4.5-5.75 V DC 12-14 V DC 11.4-14.5 V DC
Rated output power 15 W 30 W 120 W
Rated output current Ir Ta ͨ 60 °C 3.0 A 2.5 A 10 A
Derating of the output current 60 °C < Ta ͨ 70 °C 2.5 %/°C 2.5 %/°C
Maximum deviation with load change statical ±2 % ±0.5 % ±1 % (single mode)
±5 % (parallel mode)
Control time change of output voltage within the ±1 % ±0.5 % ±0.5 %
input voltage range
< 2 ms
Starting time after applying the supply voltage at Ir max. 1 s
with 3500 μF -
max. 2 s -
with 7000 μF max. 1.5 s - max. 1.5 s
Rise time at rated load max. 150 ms
with 3500 μF - max. 500 ms -
with 7000 μF max. 500 ms - max. 500 ms
Fall time max. 150 ms
Residual ripple and switching peaks BW = 20 MHz 50 mV
Parallel connection yes, to enable redundancy configurable, to
Series connection yes, to increase voltage increase power,up to 3
Resistance to reverse feed 1 s - max. 7.5 V DC 1 s - max.18 V DC devices,
min. 0.1 Ir - max. 0.9 Ir
yes, to increase
voltage, max. 2
devices
max. 18 V DC
Output circuit - No-load, overload and short-circuit behaviour
Characteristic curve of output Hiccup-mode U/I characteristic curve
Short-circuit protection continuous short-circuit proof
Short-circuit behaviour Hiccup-mode continuation with output power limiting
Overload protection output power limiting
No-load protection continuous no-load stability
Starting of capacitive loads 7000 μF 3500 μF 7000 μF