Page 24 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 24
MS116, MS132, MS165, MO132, MO165, MS132-T
Technical data
Main circuit – Utilization characteristics according to IEC/EN
Type MS116 MS132 MS165 MO132 MO165 MS132-T
Standards IEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1
2 Rated operational voltage U e 690 V AC 690 V AC / 690 V AC 690 V AC 690 V AC 690 V AC
250 V DC
Rated frequency 50/60 Hz DC, 50/60 Hz DC, 50/60 Hz 50/60 Hz DC, 50/60 Hz 50/60 Hz
Operational frequency 50/60 Hz 0 ... 400 Hz 0 ... 400 Hz 0 ... 400 Hz 0 ... 400 Hz 0 ... 400 Hz
Trip class 10A 10 10 - - 10
Number of poles 3
Duty time 100 %
Mechanical durability 100000 cycles 100000 cycles 50000 cycles 100000 cycles 50000 cycles 100000 cycles
Electrical durability up to 16 A 100000 cycles 50000 cycles 25000 cycles 50000 cycles 25000 cycles 50000 cycles
20 ... 65 A 50000 cycles 50000 cycles 25000 cycles 50000 cycles 25000 cycles 50000 cycles
Rated impulse withstand voltage U imp 6 kV 6 kV 8 kV 6 kV 8 kV 6 kV
Rated insulation voltage U i 690 V 690 V 1000 V 690 V 1000 V 690 V
Rated operational current I e See ordering details
Rated operational current DC-5 I e - See "Rated See "Rated - See "Rated -
3 conducting paths in series up to 250 V operational operational operational
current I " current I " current I " e
e
e
Rated instantaneous short-circuit current setting I See ordering details
i
Rated service short-circuit breaking capacity I cs See table "Short-circuit breaking capacity and back-up fuses"
Rated ultimate short-circuit breaking capacity I See table "Short-circuit breaking capacity and back-up fuses"
cu
Rated service short-circuit breaking capacity DC I cs - 10 kA 100 kA - 100 kA -
3 conducting paths in series up to 250 V
Short-circuit breaking capacity and back-up fuses
l CS Rated service short-circuit breaking capacity
l Rated ultimate short-circuit breaking capacity
CU
I Prospective short-circuit current at installation location
CC
Note: Maximum rated current of the back-up fuses if I > I CS
CC
Type 230 V AC 400 V AC 440 V AC 500 V AC 690 V AC
I I CU gG, aM I CS I CU gG, aM I CS I CU gG, aM I CS I CU gG, aM I CS I CU gG, aM
CS
kA kA A kA kA A kA kA A kA kA A kA kA A
MS116-0.16 50 50 - 1) 50 50 - 1) 30 30 - 1) 30 30 - 1) 30 30 - 1)
MS116-0.25 50 50 - 1) 50 50 - 1) 30 30 - 1) 30 30 - 1) 30 30 - 1)
MS116-0.4 50 50 - 1) 50 50 - 1) 30 30 - 1) 30 30 - 1) 30 30 - 1)
MS116-0.63 50 50 - 1) 50 50 - 1) 30 30 - 1) 30 30 - 1) 30 30 - 1)
MS116-1.0 50 50 - 1) 50 50 - 1) 30 30 - 1) 30 30 - 1) 30 30 - 1)
MS116-1.6 50 50 - 1) 50 50 - 1) 30 30 - 1) 30 30 - 1) 30 30 - 1)
MS116-2.5 50 50 - 1) 50 50 - 1) 10 10 25 2) 10 10 25 2) 5 5 25 2)
MS116-4.0 50 50 - 1) 50 50 - 1) 6 6 25 2) 6 6 25 2) 2 2 25 2)
MS116-6.3 50 50 - 1) 50 50 - 1) 6 6 63 2) 6 6 63 2) 2 2 40 2)
MS116-10 50 50 - 1) 50 50 - 1) 6 6 63 2) 6 6 63 2) 2 2 50 2)
MS116-12 25 25 80 2) 25 25 80 2) 6 6 63 2) 6 6 63 2) 2 2 50 2)
MS116-16 16 16 80 2) 16 16 80 2) 4 4 63 2) 4 4 63 2) 2 2 63 2)
MS116-20 10 15 125 2) 10 15 125 2) 3 6 125 2) 3 4 125 2) 2 2 80 2)
MS116-25 10 15 125 2) 10 15 125 2) 3 6 125 2) 3 4 125 2) 2 2 100 2)
MS116-32 10 10 125 2) 10 10 125 2) 3 6 125 2) 3 4 125 2) 2 2 100 2)
No back-up fuse required, because short-circuit proof up to 50 kA
1)
2) Rated back-up fuse for short-circuit up to 50 kA
2CDC131062C0201
2/16 | ABB