Page 24 - Motor_protection_and_control_Manual_motor_starters_ contactors
P. 24

MS116, MS132, MS165, MO132, MO165, MS132-T

       Technical data





       Main circuit – Utilization characteristics according to IEC/EN
       Type                                MS116       MS132      MS165       MO132       MO165      MS132-T
       Standards                           IEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1
    2  Rated operational voltage U e       690 V AC    690 V AC /   690 V AC  690 V AC    690 V AC   690 V AC
                                                       250 V DC
       Rated frequency                     50/60 Hz    DC, 50/60 Hz  DC, 50/60 Hz  50/60 Hz  DC, 50/60 Hz  50/60 Hz
       Operational frequency               50/60 Hz    0 ... 400 Hz  0 ... 400 Hz  0 ... 400 Hz  0 ... 400 Hz  0 ... 400 Hz
       Trip class                          10A         10         10          -           -          10
       Number of poles                     3
       Duty time                           100 %
       Mechanical durability               100000 cycles  100000 cycles  50000 cycles  100000 cycles  50000 cycles  100000 cycles
       Electrical durability        up to 16 A 100000 cycles   50000 cycles  25000 cycles  50000 cycles  25000 cycles  50000 cycles
                                    20 ... 65 A 50000 cycles  50000 cycles  25000 cycles  50000 cycles  25000 cycles  50000 cycles
       Rated impulse withstand voltage U imp  6 kV     6 kV       8 kV        6 kV        8 kV       6 kV
       Rated insulation voltage U i        690 V       690 V      1000 V      690 V       1000 V     690 V
       Rated operational current I e       See ordering details
       Rated operational current DC-5 I e  -           See "Rated   See "Rated   -        See "Rated   -
       3 conducting paths in series up to 250 V        operational    operational         operational
                                                       current I "  current I "           current I " e
                                                                        e
                                                            e
       Rated instantaneous short-circuit current setting I  See ordering details
                                    i
       Rated service short-circuit breaking capacity I cs  See table "Short-circuit breaking capacity and back-up fuses"
       Rated ultimate short-circuit breaking capacity I  See table "Short-circuit breaking capacity and back-up fuses"
                                   cu
       Rated service short-circuit breaking capacity DC I cs  -  10 kA  100 kA  -         100 kA     -
       3 conducting paths in series up to 250 V
       Short-circuit breaking capacity and back-up fuses
       l CS  Rated service short-circuit breaking capacity
       l  Rated ultimate short-circuit breaking capacity
       CU
       I  Prospective short-circuit current at installation location
       CC
       Note: Maximum rated current of the back-up fuses if I  > I CS
                                      CC
       Type      230 V AC           400 V AC           440 V AC           500 V AC            690 V AC
                 I      I CU  gG, aM  I CS  I CU  gG, aM  I CS  I CU  gG, aM  I CS  I CU  gG, aM  I CS  I CU  gG, aM
                  CS
                 kA     kA    A     kA     kA    A     kA     kA    A     kA     kA    A      kA    kA    A
       MS116-0.16  50   50    -  1)  50    50    -  1)  30    30    -  1)  30    30    -  1)  30    30    -  1)
       MS116-0.25  50   50    -  1)  50    50    -   1)  30   30    -  1)  30    30    -  1)  30    30    -  1)
       MS116-0.4  50    50    -  1)  50    50    -  1)  30    30    -  1)  30    30    -  1)  30    30    -  1)
       MS116-0.63  50   50    -  1)  50    50    -   1)  30   30    -  1)  30    30    -  1)  30    30    -  1)
       MS116-1.0  50    50    -  1)  50    50    -   1)  30   30    -  1)  30    30    -  1)  30    30    -  1)
       MS116-1.6  50    50    -  1)  50    50    -   1)  30   30    -  1)  30    30    -  1)  30    30    -  1)
       MS116-2.5  50    50    -  1)  50    50    -   1)  10   10    25  2)  10   10    25  2)  5    5     25  2)
       MS116-4.0  50    50    -  1)  50    50    -   1)  6    6     25  2)  6    6     25  2)  2    2     25  2)
       MS116-6.3  50    50    -  1)  50    50    -   1)  6    6     63  2)   6   6     63  2)  2    2     40  2)
       MS116-10  50     50    -  1)  50    50    -   1)  6    6     63  2)  6    6     63  2)  2    2     50  2)
       MS116-12   25    25    80  2)  25   25    80  2)  6    6     63  2)  6    6     63  2)  2    2     50  2)
       MS116-16  16     16    80  2)  16   16    80  2)  4    4     63  2)  4    4     63  2)  2    2     63  2)
       MS116-20  10     15    125  2)  10  15    125  2)  3   6     125  2)  3   4     125  2)  2   2     80  2)
       MS116-25  10     15    125  2)  10  15    125  2)  3   6     125  2)  3   4     125  2)  2   2     100  2)
       MS116-32  10     10    125  2)  10  10    125  2)  3   6     125  2)  3   4     125  2)  2   2     100  2)

         No back-up fuse required, because short-circuit proof up to 50 kA
       1)
       2)  Rated back-up fuse for short-circuit up to 50 kA





                                                                                                                  2CDC131062C0201






       2/16  |  ABB