Page 102 - Current & voltage sensors catalog
P. 102

Electronic voltage detectors
       Instructions for mounting and wiring VD detectors





       3 - 1st switching on of the detector
       After applying high voltage to the primary terminals of the VD voltage detector, pay attention to the following points:
          – do not touch the HT terminals (high voltage) of the VD voltage detector
          – do not try to remove the lenses of the LEDs

       Checking correct functioning
       The VD voltage detector LEDs should flash about every 0.5 seconds as soon as the dangerous voltage U ON is passed. The LEDs should remain extin-
       guished below U OFF, (see the detailed characteristics of the VD1500 voltage detector). In the event that LEDs do not work when high voltage is applied:
          – electrically isolate the system
          – make sure that no residual voltage is present in the VD voltage detector (voltmeter or other means)
          – check that the VD voltage detector wiring is correct (this may explain why the LEDs do not work)
    4  If no faults are found in the installation, carry out a complete replacement of the voltage detector.
       Please contact your distributor for further information on this subject or refer to the document Voltage Detector usage - Preventive and Curative
       Maintenance.
























































                                                                                                                  1SBC140070S0201







       100  |  ABB