Page 372 - EPR Catalog 2015
P. 372

Logic relays
Technical data

Data at Ta = 25 °C and rated values, if nothing else indicated.

Type                                                      CL-LER.18DC2, CL-LET.20DC2                        CL-LER.18AC2
                                                                          24 V DC                           115 / 230 V AC
Input circuit - Digital inputs
                                                                                      0-40 V AC (sinusoidal)
Number                                             12                                 79-264 V AC (sinusoidal)
                                                                                      50-60 Hz
Inputs can be used as analog inputs                -                                  12x0.25 mA (at 115 V AC, 60 Hz, R1-R12),
                                                                                      12x0.5 mA (at 230 V AC, 50 Hz, R1-R12)
Indication of operational states                   -                                  80 ms (at 50 Hz, I1-I12, R1-R12),
                                                                                      66 2/3 ms (at 60 Hz, I1-I12, R1-R12)
Electrical isolation  from voltage supply no                                          20 ms (at 50 Hz, I1-I12, R1-R12),
                                                                                      16 2/3 ms (at 60 Hz, I1-I12, R1-R12)
                      between digital inputs no                                       80 ms (at 50 Hz, I1-I12, R1-R12),
                                                                                      66 2/3 ms (at 60 Hz, I1-I12, R1-R12)
                                  from the outputs yes                                20 ms (at 50 Hz, I1-I12, R1-R12),
                                                                                      16 2/3 ms (at 60 Hz, I1-I12, R1-R12)
                                from PC interface, no                                 -
                                                                                      typ. 40 m (I1-I6, I9-I12, R1-R12),
                                     memory                                           typ. 100 m (I7, I8)

                                  module, CL-NET,

                                     CL-LINK

Rated operational                                        24 V DC
voltage Ue                        Ue on „0“ signal < 5 V DC (I1-I12, R1-R12)

Rated frequency                   Ue on „1“ signal -
Input current
on „1“ signal                                            -
                                                         3.3 mA (at 24 V DC, R1-R12)

       Time delay                  debounce ON 20 ms
                                  debounce OFF typ. 0.25 ms (R1-R12)
6 from „0“ to „1“

Time delay                         debounce ON 20 ms
from „1“ to „0“                   debounce OFF -

Cable length (unshielded)                          100 m
Maximum cable length per input                     -

6/13 ABB | Catalog Electronic Products and Relays 2015 | 2CDC 110 004 C02010
   367   368   369   370   371   372   373   374   375   376   377